OICEW-7-1D
Connect ship service diesel generator to main switchboard
Condition
Aboard a dead ship or in simulator, given access to generator and proper tools, approved instruction, and safe working environment.
Performance requirement
Behavior | Standard |
---|---|
The student will: | During assessment, the student shall, at a minimum: |
Check that system is ready to start |
Meet requirements of OICEW 7-1B |
Start the generator |
Turn generator mode selector switch to manual Turn generator starting switch to start |
Check that generator starts properly |
Check:
|
Operate generator to achieve conditions suitable for synchronization |
Adjust generator to normal operating speed Place voltage regulator in manual Excite field Adjust frequency to 60 hz Adjust voltage to 120V |
synchronize incoming generator with bus |
Turn on synchroscope Match voltage and frequency with bus Close main breaker when generators are in phase Turn off synchroscope |
Adjust load on incoming generator |
Transfer voltage regulator to automatic Balance active (kw) load Balance reactive (kvar) load |
See the Engineering Assessment Guidelines for additional specifications of behavior and standards.
Note: This assessment supports KUP OICEW-B1.1, and is assessed in EN-3233 Steam and Gas Turbines.