The candidate takes the following actions, describing them as they are performed:
-
Inspects alternator for loose cable connections, brush rigging, and loose items that may damage unit during start-up;
-
Inspects coupling between turbine/reduction gear and alternator for readiness;
-
Inspects governor unit, reduction gear casing, and bearing housings for indications of lubrication leaks;
-
Inspects manual over-speed trip for excessive wear;
-
Determines level of lube-oil in sump and adds lube-oil as necessary;
-
Manually trips and resets over-speed trip to determine operation without binding;
-
Inspects auxiliary circulator pump and its piping for leaks and cracks;
-
Verifies that sea suction and discharge valves are open to auxiliary circulator;
-
Inspects auxiliary condensate pump and its piping for leaks and cracks;
-
Verifies that hot well condensate level is visible;
-
Verifies that suction, discharge, and vent line valves to auxiliary condensate pump are open;
-
Inspects auxiliary circulator and condensate pump motor controllers for readiness;
-
Starts auxiliary circulator;
-
Vents-off condenser heads and observes stabilizing of circulated water pressure;
-
Starts auxiliary condensate pump;
-
Adjusts opening of re-circulating valve to maintain visible level of condensate in hot well;
-
Returns to operating level and applies gland seal steam to turbine rotor;
-
Admits operating steam to air ejectors, adjusting supply pressure as necessary;
-
Determines visible level in hot well, adjusting re-circulating valve as necessary;
-
Starts lube-oil supply to unit when vacuum reaches 18-22 inches (obtain assistance if pump is hand-operated);
-
Sets throttle valve;
-
Slowly opens throttle valve, gradually increasing turbine rotating speed;
-
Allows unit to rotate without load for even warming;
-
Applies lube-oil and alternator cooler water supply as necessary; and
-
Takes proper action to prevent safety and pollution violations.