Visually inspects the boiler to ensure that boiler firesides and watersides are properly closed up and that all manholes, hand holes, and access plates are properly secured;
-
Wipes up any oil accumulations in the furnace or air casing;
-
Checks closed bottom and surface blow valves; waterwall and economizer header drain valves; chemical feed and main and auxiliary feed stop check valves; main and auxiliary and soot blower steam stop valves, and the gauge glass drain valve;
-
Checks open the steam drum vent valve; superheater drain and vent valves; gauge glass cutoff valves; instrument and gauge root valves; and the feedwater stop valves;
-
Vents the economizer; close valve when water evident at vent;
-
Brings the boiler water level to 1 inch from the bottom of the gauge glass, filling or draining the boiler as necessary and makes sure to verify the ability to feed the boiler;
-
Blows down the boiler water level gauge glass to insure accuracy, leaving several inches of water in the glass;
-
Visually inspects the boiler and checks for water leaks;
-
Eases off on all steam stop valves and re-closes them hand tight;
-
Inspects and cleans all fuel oil strainers and ensures atomizers are made up with clean tips;
-
Ensures the air register doors operate freely;
-
Inserts a burner with small size tip into burner tube;
-
Starts forced draft fan, adjust damper, open register(s), and purges the furnace;
-
Ensures burner fuel oil root valves are closed; opens recirculating valve;
-
When fuel oil reaches proper temperature, reduces purging air volume and uses a torch or electric igniter to light burner;
-
Watches rise in steam drum water level and feeds as necessary;
-
When drum pressure reaches the recommended pressure, closes superheater drain and drum vent;
-
Continues slow fire and feeding until drum pressure is nearly line pressure;
-
Opens auxiliary steam stop to “float” the boiler online;
-
Closes superheater vent; puts feedwater and firing on “auto;”
-
Ensures that all operations are in accordance with manufacturer’s recommended procedures; and
-
Takes proper action to prevent safety and pollution violations.